Final | 2/27/2008 | 2/28/2008 | 2/28/2008 | A | PASS |
Bob Reichert
|
|
|
DAVE CALL PRIOR TO HEADING TO SITE Phone #: ###-#### Internet Inspection Request from: Sean DeLacy see ri, ok to final
|
Electrical Rough-In | 2/28/2008 | 2/28/2008 | 2/28/2008 | A | PASS |
Bob Reichert
|
|
|
DAVE CALL PRIOR TO HEADING TO SITE Phone #: ###-#### Internet Inspection Request from: Sean DeLacy corrections made, ok to cover ceiling
|
Final | 2/26/2008 | 2/27/2008 | 2/27/2008 | A | FAIL |
Bob Reichert
|
|
|
DAVE CALL PRIOR TO HEADING TO SITE Phone #: ###-#### Internet Inspection Request from: Sean DeLacy met contractor, left correction notice, BCC no violations shall be retained, NEC 300.11(A) raceways shall be secured in place, and not on grid, 330.30(B) mc cable shall be secured within 12" of box,358.30(A) emt shall be secured within 3' of box, 408.4 circuit directory shall be clear, concise, complete, and explanatory for each circuit, 725.3(B) abandoned class2,3, pltc cables shall be removed, 725.8 cass1,2,3 cables shall be installed in a workman like manner and be supported
|
Final | 2/26/2008 | 2/27/2008 | 2/26/2008 | A | CANC |
Jack Frank
|
|
|
STEVE Phone #: ###-#### Internet Inspection Request from: Sean DeLacy Inspection cancelled from web by: Sean DeLacy
|
Electrical Rough-In | 2/14/2008 | 2/15/2008 | 2/15/2008 | A | PART |
Jack Frank
|
|
|
STEVE UNDERGROUND Phone #: ###-#### Internet Inspection Request from: Sean DeLacy u/g ok
|
Electrical Rough-In | 2/13/2008 | 2/13/2008 | 2/13/2008 | P | PASS |
Mike Kinnear
|
|
|
MORGAN RUSSELL - WALL ROUGH IN Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok cover walls only
|