Temporary Service | 2/12/2008 | 2/13/2008 | 2/13/2008 | A | PASS |
Bob Reichert
|
|
|
alan Phone #: ###-#### corrections made, t/s o/h n ok
|
Temporary Service | 2/11/2008 | 2/12/2008 | 2/12/2008 | A | FAIL |
Bob Reichert
|
|
|
alan Phone #: ###-#### called, left correction notice, BCC job id sticker shall be posted, NEC 312.5 all conductors entering enclosure shall have abrasion protection, 250.24(A) gec shall connect to grounded service conductor, fee due
|