Final | 5/16/2008 | 5/16/2008 | 5/16/2008 | P | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ok no card
|
Permanent Service | 2/26/2008 | 2/27/2008 | 2/27/2008 | A | PASS |
Bob Reichert
|
|
|
Job site contact: Gene ###-#### Phone #: ###-#### Internet Inspection Request from: Tracy Robertson corrections made, p/s u/g n ok, 5 meters required
|
Rough-In Permanent Service | 2/14/2008 | 2/14/2008 | 2/14/2008 | P | CANC |
Bob Reichert
|
|
|
Sorry for the am/pm confusion. Happy Valentine Day!! Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson see ri and p/s
|
Permanent Service | 2/14/2008 | 2/14/2008 | 2/14/2008 | P | FAIL |
Bob Reichert
|
|
|
Sorry for the am/pm confusion. Happy Valentine Day!! Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson told electrician, left correction notice, NEC 110.26(F)(2)) depth of working space shall be provided at service- no other equipment shall be located in this zone
|
Electrical Rough-In | 2/14/2008 | 2/14/2008 | 2/14/2008 | P | PASS |
Bob Reichert
|
|
|
Sorry for the am/pm confusion. Happy Valentine Day!! Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson ric ok
|
Rough-In Permanent Service | 2/13/2008 | 2/14/2008 | 2/14/2008 | A | NR |
Mike Kinnear
|
|
|
Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson t/w electrian job not ready
|