Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberELE08-00373
StatusFinaled
Name ANDERSON & WOOD CONSTRUCTION
Site Address 5600 E WARM SPRINGS AVE
Project Name 
Customer Number07-7060
ePlanReview 
Description
Electrical Permit - New: East Boise Jr. High School Electrical Construction //$10,000 of this value split out to create Ele09-01496//8/14/09 LEG
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final7/2/20097/2/20097/2/2009PPASS
DetailsDoug A Poedy
John Phone #: ###-#### Ok final, signed co
Final7/1/20097/1/20097/1/2009PPART
DetailsDoug A Poedy
Area A please-John Phone #: ###-#### ok final last section. only need to inspections on score boards and rooftop.
Final6/30/20096/30/20096/30/2009PPART
DetailsDoug A Poedy
areas b & c please-John Phone #: ###-#### Ok final B@C
Final6/25/20096/25/20096/25/2009PPART
DetailsMike Kinnear
john - areas f,g & h Phone #: ###-#### ok part final anop.
Final6/24/20096/24/20096/24/2009PPART
DetailsMike Kinnear
john Phone #: ###-#### Ok partial final area d and e classrooms.
Electrical Rough-In5/6/20095/6/20095/6/2009PPART
DetailsMike Kinnear
John Phone #: ###-#### ok cover ceiling anop
Electrical Rough-In4/21/20094/22/20094/22/2009APART
DetailsBob Reichert
john Phone #: ###-#### ok to cover ceilings anop
Electrical Rough-In4/9/20094/9/20094/9/2009PPART
DetailsMike Kinnear
John Phone #: ###-#### ok cover ceilings anop
Electrical Rough-In3/30/20093/31/20093/31/2009APART
DetailsPat Lass
john Phone #: ###-####
anop
Electrical Rough-In3/23/20093/23/20093/23/2009PPART
DetailsMike Kinnear
John Phone #: ###-#### ok cover ceiling anop
Electrical Rough-In3/18/20093/18/20093/18/2009PPART
DetailsMike Kinnear
john Phone #: ###-#### ok cover ceilings anop
Electrical Rough-In3/16/20093/16/20093/16/2009PPASS
DetailsMike Kinnear
John Phone #: ###-#### ok cover ceiling anop
Electrical Rough-In3/2/20093/3/20093/3/2009APASS
DetailsMike Kinnear
john Phone #: ###-#### ok cover ceiling anop
Electrical Rough-In2/19/20092/19/20092/19/2009PPART
DetailsMike Kinnear
John- ceiling Phone #: ###-#### ok cover ceiling anop
Electrical Rough-In2/13/20092/13/20092/13/2009PPART
DetailsJack Frank
John Phone #: ###-#### ceilings anop ok
Electrical Rough-In2/9/20092/10/20092/10/2009APART
DetailsBob Reichert
john Phone #: ###-#### ceiling anop ok to cover
Electrical Rough-In2/4/20092/4/20092/4/2009PPART
DetailsPat Lass
john Note: above ceiling Phone #: ###-####
ceilings anop
Electrical Rough-In2/3/20092/3/20092/3/2009PFAIL
DetailsJack Frank
john Note: above ceiling Phone #: ###-####
corr. met contr, 300.11 shall not use fixture wire to support cables code states wires shall be attached to structure, and ceiling assembly
Electrical Rough-In1/29/20091/29/20091/29/2009PPART
DetailsMike Kinnear
john Note: drop in ceiling Phone #: ###-#### ok cover drop ceiling anop
Permanent Service1/29/20091/29/20091/29/2009PPASS
DetailsMike Kinnear
john Phone #: ###-#### p/s u/g n ok
Electrical Rough-In1/23/20091/23/20091/23/2009PPART
DetailsJack Frank
john Phone #: ###-#### anop ok,
see failed added r/i request for electrical rm
Electrical Rough-In1/23/20091/23/20091/23/2009PFAIL
DetailsJack Frank
john Phone #: ###-#### corr. posted for electrical rm upstairs area F remove exhaust fan, and makeup air ducts from above panels, no ceiling is not a structural as noted in 110.26 (F)(1)
Electrical Rough-In1/15/20091/16/20091/16/2009APASS
DetailsMike Kinnear
john Phone #: ###-#### ok cover walls only anop
Electrical Rough-In12/23/200812/24/200812/24/2008PPASS
DetailsMike Kinnear
john Phone #: ###-#### ok cover fire ceiling anop
Electrical Rough-In12/18/200812/18/200812/18/2008PPART
DetailsPat Lass
john Phone #: ###-####
walls and hard lids ok
anop
Electrical Rough-In12/3/200812/3/200812/3/2008PPASS
DetailsMike Kinnear
john Phone #: ###-#### ok cover walls & soffit anop
Electrical Rough-In11/18/200811/18/200811/18/2008PPASS
DetailsMike Kinnear
John Phone #: ###-#### ok cover hard lid fire ceiling anop
Electrical Rough-In11/6/200811/6/200811/6/2008PPASS
DetailsMike Kinnear
john Phone #: ###-#### ok cover walls, hard lid ceilings, & hard lid fire ceiling anop
Electrical Rough-In10/24/200810/27/200810/27/2008APASS
DetailsMike Kinnear
john Phone #: ###-#### ok cover walls, hard lid ceilings, & fire ceiling anop
Electrical Rough-In9/5/20089/5/20089/5/2008PPASS
DetailsMike Kinnear
JOHN Phone #: ###-#### ok cover walls anop
ELE-Aging Inspection7/23/20087/23/20087/25/2008 NR
DetailsMike Kinnear
job under construction
Electrical Rough-In5/13/20085/13/20085/13/2008PPASS
DetailsMike Kinnear
don Note: underslap Phone #: ###-#### ok cover under slab conduit anop
Temporary Service5/12/20085/12/20085/12/2008PCANC
DetailsMike Kinnear
john - underground and temp service Phone #: ###-#### wrong type inspection
Conference5/12/20085/12/20085/12/2008PPASS
DetailsMike Kinnear
john - underground and temp service Phone #: ###-#### regarding temp service with transformer
Electrical Rough-In5/2/20085/2/20085/2/2008PPASS
DetailsMike Kinnear
john - underground Phone #: ###-#### ok cover under ground conduit anop
Electrical Rough-In4/17/20084/17/20084/17/2008PPASS
DetailsMike Kinnear
john Phone #: ###-#### ok cover under slab conduit anop
Rough-In Permanent Service4/15/20084/15/20084/15/2008PCANC
DetailsMike Kinnear
john - underslab Phone #: ###-#### wrong type inspection
Electrical Rough-In4/15/20084/15/20084/15/2008PPASS
DetailsMike Kinnear
john - underslab Phone #: ###-#### ok cover under slab conduit anop
Electrical Rough-In4/1/20084/1/20084/1/2008PPASS
DetailsMike Kinnear
john Note: underground Phone #: ###-#### Note: come in hwy 21 ok cover under slab conduit anop
Electrical Rough-In3/27/20083/27/20083/27/2008PPASS
DetailsMike Kinnear
john - underground - come in off of idaho city hwy 21 Phone #: ###-#### ok cover under slab conduit anop
Electrical Rough-In3/25/20083/25/20083/25/2008PPASS
DetailsMike Kinnear
JOHN nOTE: UNDERGROUND Phone #: ###-#### Note: come in on hwy 21 ok cover concrete encased electroded & cover under slab conduit anop
Electrical Rough-In3/13/20083/13/20083/13/2008PPASS
DetailsMike Kinnear
jon - underground Phone #: ###-#### ok cover under ground conduit anop
Electrical Rough-In3/10/20083/11/20083/11/2008APASS
DetailsMike Kinnear
john Phone #: ###-#### ok cover under ground & under slab conduit anop
Electrical Rough-In3/4/20083/4/20083/4/2008PPASS
DetailsMike Kinnear
john Note: underground Phone #: ###-#### ok cover under ground conduit anop
Electrical Rough-In2/27/20082/27/20082/27/2008PPASS
DetailsMike Kinnear
John (underground); Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok cover under ground conduit anop
Electrical Rough-In2/26/20082/26/20082/26/2008PPART
DetailsMike Kinnear
john Note: underground Phone #: ###-#### ok cover under ground conduit anop
Electrical Rough-In2/20/20082/20/20082/20/2008PPART
DetailsMike Kinnear
john - underground - please call 1/2 hr prior to inspection Phone #: ###-#### ok cover under ground conduit & concrete incases electrode anop