Final | 6/24/2008 | 6/24/2008 | 6/24/2008 | P | PASS |
Bob Reichert
|
|
|
Dave Phone #: ###-#### corrections made, ok to final, no esc this project
|
Final | 6/16/2008 | 6/16/2008 | 6/16/2008 | P | FAIL |
Bob Reichert
|
|
|
Dave Phone #: ###-#### called contractor, left correction notice,NEC 408.4 shall provide circuit directory that is clear, concise and explanatory, 422.31(B) shall provide water heater disconnect, 406.4(D) receptacle faces shall be flush with or project from faceplate, BCC address shall be posted on dwelling and services, no esc
|
Permanent Service | 3/20/2008 | 3/21/2008 | 3/21/2008 | A | PASS |
Jack Frank
|
|
|
dave Phone #: ###-#### p/s o/h new ok
|
Permanent Service | 3/14/2008 | 3/14/2008 | 3/14/2008 | P | FAIL |
Jack Frank
|
|
|
dave Phone #: ###-#### corr called shall derate conductors on raceways, 200.7 re ID neutrals used as phases, seal hole top of j box, 250.148 terminate all equip grds together in jbox
|
Permanent Service | 3/5/2008 | 3/6/2008 | 3/6/2008 | A | FAIL |
Jack Frank
|
|
|
dave Phone #: ###-#### 110.3(B) manufactures instructions load conductors shall not exit through top endwall, alum grd clamp not approved for contact with earth, corr. called
|
Final | 2/28/2008 | 2/29/2008 | 2/29/2008 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 2/28/2008 at 4:58:12 PM. Contact: ###-####. called, left message, left correction notice, NEC 250.53(D)(2) shall supplement metal underground water pipe by type specified in 250.52(A)(2) thru (A)(7)
|
Electrical Rough-In | 2/27/2008 | 2/28/2008 | 2/28/2008 | A | PASS |
Bob Reichert
|
|
|
Loren; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ric ok
|