Electrical Rough-In | 2/27/2008 | 2/28/2008 | 2/28/2008 | A | PASS |
Mike Kinnear
|
|
|
Thanks, Andrea. Phone #: ###-#### x0000 Internet Inspection Request from: Andrea Creek correction made ok cover ri
|
Rough-In Permanent Service | 2/25/2008 | 2/26/2008 | 2/26/2008 | A | CANC |
Bob Reichert
|
|
|
Thanks, Andrea. Phone #: ###-#### x0000 Internet Inspection Request from: Andrea Creek see ri and p/s
|
Permanent Service | 2/26/2008 | 2/26/2008 | 2/26/2008 | A | PASS |
Bob Reichert
|
|
|
Thanks, Andrea. Phone #: ###-#### x0000 Internet Inspection Request from: Andrea Creek p/s u/g n ok
|
Electrical Rough-In | 2/26/2008 | 2/26/2008 | 2/26/2008 | A | FAIL |
Bob Reichert
|
|
|
Thanks, Andrea. Phone #: ###-#### x0000 Internet Inspection Request from: Andrea Creek called contractor, left correction notice, BCC job address shall be posted, job id sticker shall be posted, boxes shall be installed for bath and micro-wave, NEC 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member, 334.30 nm cable shall be stapled within 12" of panel, 210.52(a)(1) receptacles shall be installed such that no point alonf wall space is over 6' from an outlet
|