Final | 9/30/2008 | 10/1/2008 | 10/1/2008 | A | PASS |
Bob Reichert
|
|
|
justin Phone #: ###-#### ok to final
|
Rough-In Permanent Service | 3/20/2008 | 3/21/2008 | 3/21/2008 | A | PASS |
William E Thomas
|
|
|
justin Phone #: ###-#### . .1. ri ok. .. . .2. p/s u/g n ok. .
|
Rough-In Permanent Service | 3/18/2008 | 3/19/2008 | 3/19/2008 | A | FAIL |
Bob Reichert
|
|
|
justin Phone #: ###-#### called left correction notice, BCC address shall be posted, job id sticker shall be posted, approved set of plans shall be on job, wiring shall be terminated in boxes, NEC 362.30(A) ent shall be securely fastened within 3' of box, 362.46 bushings or adapter shall be installed at box, 334.30 nm cable shall be secured within 12" of box, 314.17 conductors entering boxes shall be protected from abrasion, 110.26(F)(2) no other equipment shall be located in dedicated space about electrical equipment-lv under meter
|
Electrical Rough-In | 3/13/2008 | 3/14/2008 | 3/14/2008 | P | CANC |
Jack Frank
|
|
|
justin Phone #: ###-#### conference ok
|