Final | 5/13/2008 | 5/13/2008 | 5/13/2008 | P | PASS |
Jack Frank
|
|
|
###-#### Internet Inspection Request from: Todd Holbrook ok
|
Final | 5/12/2008 | 5/12/2008 | 5/12/2008 | P | NR |
Jack Frank
|
|
|
###-#### Internet Inspection Request from: Todd Holbrookcalled contr needs permit for p/s told him once before , and he still has not done it
|
Electrical Rough-In | 4/2/2008 | 4/3/2008 | 4/3/2008 | A | PART |
Jack Frank
|
|
|
pool grid bond Tom ###-#### Internet Inspection Request from: Todd Holbrook e grid and potting ok talked with contr needs to update permit for a p/s need to check grd and bonding, also old service panel now a subpanel check grd neutral isolation and dryer and range for 4 wire branch circuits recepts and pigtails
|
Electrical Rough-In | 4/2/2008 | 4/2/2008 | 4/2/2008 | P | FAIL |
Jack Frank
|
|
|
tom Note: grid - pool lights Phone #: ###-#### called corr & do not cover posted 680.26(C) shall use clamps listed for concrete alum not listed also raise re-bar 11/2" off of the grd
|
Electrical Rough-In | 3/21/2008 | 3/21/2008 | 3/21/2008 | P | PART |
Jack Frank
|
|
|
tom Phone #: ###-#### u/g ok corrections made
|
Electrical Rough-In | 3/20/2008 | 3/20/2008 | 3/20/2008 | P | FAIL |
Jack Frank
|
|
|
tom - trenches Phone #: ###-#### corr called over 360 degrees of bends in1/2 of all the u/g conduit runs
|
Electrical Rough-In | 3/13/2008 | 3/13/2008 | 3/13/2008 | P | PART |
Jack Frank
|
|
|
Ground pool grid ###-#### Internet Inspection Request from: Todd Holbrook pool bond ok
|