ELE-Aging Inspection | 1/13/2010 | 1/13/2010 | 1/13/2010 | | CANC |
Jack Frank
|
|
|
|
DOC - Permit Expired | 1/13/2010 | 1/13/2010 | 1/13/2010 | A | PASS |
Jack Frank
|
|
|
|
Electrical Rough-In | 4/3/2008 | 4/4/2008 | 4/4/2008 | A | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 4/3/2008 at 8:28:41 PM. Contact: ###-####. corrections made, ric ok, 2 rooms
|
Electrical Rough-In | 3/22/2008 | 3/24/2008 | 3/24/2008 | A | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 3/22/2008 at 7:46:56 PM. Contact: ###-####. met owner, left correction notice, NEC 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member. 312.5 shall close openings in boxes and use abrasion protection, 300.14 at least 6" free conductor shall be provided where conductor enters box then spliced, 210.52(A)(1) receptacles shall be installed such that no point along floor line is more than 6' from an outlet, 334.30 nm cable shall be secured at 4 1/2' intervals, 314.17 nm cable shall be secured within 8" of box BCC all make-up shall be done
|
Conference | 3/17/2008 | 3/18/2008 | 3/18/2008 | A | DONE |
Bob Reichert
|
|
|
gary--please call a half hour prior to inspection Phone #: ###-#### talked about make-up, steel studs, 1 1/4", boxes, arc fault for bedroom, outlet spacing
|