Information based on query as of Friday, August 16, 2024.
Permit Information
Permit NumberELE08-00637
StatusExpired
Name LUKE GARY D
Site Address 2072 S PETRA AVE
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
ELE-Aging Inspection1/13/20101/13/20101/13/2010 CANC
DetailsJack Frank
DOC - Permit Expired1/13/20101/13/20101/13/2010APASS
DetailsJack Frank
Electrical Rough-In4/3/20084/4/20084/4/2008APASS
DetailsBob Reichert
Scheduled by a contractor via Hello! on 4/3/2008 at 8:28:41 PM. Contact: ###-####. corrections made, ric ok, 2 rooms
Electrical Rough-In3/22/20083/24/20083/24/2008AFAIL
DetailsBob Reichert
Scheduled by a contractor via Hello! on 3/22/2008 at 7:46:56 PM. Contact: ###-####. met owner, left correction notice, NEC 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing member. 312.5 shall close openings in boxes and use abrasion protection, 300.14 at least 6" free conductor shall be provided where conductor enters box then spliced, 210.52(A)(1) receptacles shall be installed such that no point along floor line is more than 6' from an outlet, 334.30 nm cable shall be secured at 4 1/2' intervals, 314.17 nm cable shall be secured within 8" of box BCC all make-up shall be done
Conference3/17/20083/18/20083/18/2008ADONE
DetailsBob Reichert
gary--please call a half hour prior to inspection Phone #: ###-#### talked about make-up, steel studs, 1 1/4", boxes, arc fault for bedroom, outlet spacing