Final | 8/10/2008 | 8/11/2008 | 8/11/2008 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack ok to final, no esc this project
|
Permanent Service | 7/18/2008 | 7/21/2008 | 7/21/2008 | A | PASS |
Mike Kinnear
|
|
|
Karl Peck (PH# ###-####) with Idaho Power gave us 22456 AIC, we changed panel to accomodate Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack corrections made p/s u/g n ok
|
Permanent Service | 7/7/2008 | 7/7/2008 | 7/7/2008 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack called contractor, left correction notice, NEC 110.3(A) contactor shall be listed by a nationally recognized testing lab, shall not use romex connector for gec abrasion protection, 352.30(A) rnc shall be securely fastened within 3' of panel, BCC shall verify with ipco that less than 10000 amps available for fault current level, no esc this project
|
Electrical Rough-In | 6/27/2008 | 6/27/2008 | 6/27/2008 | A | PASS |
Bob Reichert
|
|
|
ug conduit Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack u/g ok for 7 lights, no esc this project
|
Electrical Rough-In | 5/9/2008 | 5/9/2008 | 5/9/2008 | A | PART |
Bob Reichert
|
|
|
UG CONDUIT Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack ok to cover u/g west to east approx next 600', said to call next at end of run
|
Electrical Rough-In | 5/5/2008 | 5/6/2008 | 5/6/2008 | P | PASS |
Bob Reichert
|
|
|
ug conduit Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack ok to cover u/g next part from west to east stake
|
Electrical Rough-In | 4/30/2008 | 5/1/2008 | 5/1/2008 | P | PART |
Bob Reichert
|
|
|
ug conduit Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack ok to cover west 2nd part u/g
|
Electrical Rough-In | 4/30/2008 | 4/30/2008 | 4/30/2008 | P | PART |
Bob Reichert
|
|
|
ug conduit for new lights, conduit is 24" below grade bedded in sand, ends are left open Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack ok to cover west 90' u/g 2" conduit only
|