Final | 4/25/2012 | 4/26/2012 | 4/26/2012 | A | PASS |
Bob Reichert
|
|
|
Dave Phone #: ###-#### >> Inspection requested via web by Sean DeLacy ok final
|
Final | 4/23/2012 | 4/25/2012 | 4/25/2012 | A | NH |
Bob Reichert
|
|
|
Dave Phone #: ###-#### >> Inspection requested via web by Sean DeLacy called, no access
|
ELE-Aging Inspection | 3/19/2012 | 3/19/2012 | 3/21/2012 | | DONE |
Bob Reichert
|
|
|
still under construction
|
Final | 12/19/2011 | 12/20/2011 | 12/20/2011 | A | FAIL |
Bob Reichert
|
|
|
Sean. Please call prior to heading to site. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy corrections not made
|
Final | 11/10/2011 | 11/14/2011 | 11/14/2011 | A | FAIL |
Bob Reichert
|
|
|
Dave Phone #: ###-#### >> Inspection requested via web by Sean DeLacy called, left correction notice, NEC 110.26(F)(1) there shall be no foreign piping in dedicated space, 110.22 shall identify equipment, 358.30 shall secure emt within 3' of box, 408.4 shall provide panel schedules
|
Final | 11/3/2011 | 11/4/2011 | 11/4/2011 | P | NR |
Bob Reichert
|
|
|
Jason Phone #: ###-#### >> Inspection requested via web by Sean DeLacy still working basement
|
Final | 11/3/2011 | 11/3/2011 | 11/3/2011 | P | CANC |
Bob Reichert
|
|
|
Jason Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Inspection cancelled from web by: Sean DeLacy
|
ELE-Aging Inspection | 10/6/2011 | 10/6/2011 | 10/6/2011 | | DONE |
Bob Reichert
|
|
|
still under construction
|
ELE-Aging Inspection | 7/7/2011 | 7/7/2011 | 7/7/2011 | | DONE |
Bob Reichert
|
|
|
still under construction
|
Permanent Service | 4/7/2011 | 4/7/2011 | 4/7/2011 | A | PASS |
Bob Reichert
|
|
|
Dave Phone #: ###-#### >> Inspection requested via web by Sean DeLacy p/s u/g n ok, 2 meters
|
Rough-In Permanent Service | 4/5/2011 | 4/5/2011 | 4/5/2011 | P | NR |
Bob Reichert
|
|
|
Scott Phone #: ###-#### >> Inspection requested via web by Sean DeLacy need to change grounding, add identification
|
ELE-Aging Inspection | 3/28/2011 | 3/28/2011 | 3/28/2011 | | DONE |
Bob Reichert
|
|
|
still under construction
|
ELE-Aging Inspection | 6/8/2009 | 6/8/2009 | 6/8/2009 | | DONE |
Jack Frank
|
|
|
|
DOC - Permit Expired | 6/8/2009 | 6/8/2009 | 6/8/2009 | A | PASS |
Jack Frank
|
|
|
no action on permit
|
ELE-Aging Inspection | 3/24/2009 | 3/24/2009 | 3/26/2009 | | DONE |
Bob Reichert
|
|
|
suc, no activity
|
ELE-Aging Inspection | 1/19/2009 | 1/19/2009 | 1/23/2009 | | DONE |
Bob Reichert
|
|
|
suc
|
Electrical Rough-In | 11/17/2008 | 11/18/2008 | 11/18/2008 | A | PASS |
Mike Kinnear
|
|
|
JASON SLAB Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok cover conduit in slab first floor only
|
Electrical Rough-In | 9/4/2008 | 9/5/2008 | 9/5/2008 | P | PART |
Bob Reichert
|
|
|
MORGAN Phone #: ###-#### Internet Inspection Request from: Sean DeLacy east building north 1/2 slab only ok to pour
|
Electrical Rough-In | 4/8/2008 | 4/9/2008 | 4/9/2008 | A | PASS |
Bob Reichert
|
|
|
MORGAN UFFER GROUND Phone #: ###-#### Internet Inspection Request from: Sean DeLacy concrete encased electrode ok to pour east unit by peasley street
|