Final | 6/27/2008 | 6/27/2008 | 6/27/2008 | P | PASS |
Bob Reichert
|
|
|
Jeremy Phone #: ###-#### called contractor, ok to final
|
Rough-In Permanent Service | 4/17/2008 | 4/18/2008 | 4/18/2008 | A | CANC |
Bob Reichert
|
|
|
Jeremy; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok done 4-10-08 by 336 ric ok, p/s u/g n ok
|
Permanent Service | 4/9/2008 | 4/10/2008 | 4/10/2008 | A | PASS |
Pat Lass
|
|
|
jeremy Phone #: ###-#### P/S U/G N Ok
|
Electrical Rough-In | 4/10/2008 | 4/10/2008 | 4/10/2008 | P | PASS |
Pat Lass
|
|
|
jeremy Phone #: ###-####
|
Rough-In Permanent Service | 4/8/2008 | 4/8/2008 | 4/8/2008 | P | FAIL |
Bob Reichert
|
|
|
jeremy-- the n.w. unit Phone #: ###-#### called, left correction notice, NEC 250.52(A)(3) shall provide concrete encased electrode, 314.20 in walls of combustible material, boxes shall be flush with finished surface, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, BCC shall provide address, main breaker, wire empty boxes, and provide boxes for mbr bath lights,
|