Final | 5/13/2008 | 5/19/2008 | 5/19/2008 | P | PASS |
Bob Reichert
|
|
|
questions on electrical call Corey ###-#### homeowner ####-#### CALL BEFORE YOU GO Internet Inspection Request from: Yolanda Morris corrections made, ok to final
|
Final | 4/17/2008 | 4/18/2008 | 4/18/2008 | P | FAIL |
Bob Reichert
|
|
|
PLEASE CALL MR.PARKER BEFORE YOU GO-- reinspection. thank you! Phone #: ###-#### Internet Inspection Request from: Yolanda Morris called contractor, corrections to outside gfci and receptacle by furnace not made, rest ok, told to recall
|
Final | 4/8/2008 | 4/9/2008 | 4/9/2008 | P | FAIL |
Bob Reichert
|
|
|
adding circuit for furnace and heat pump, any questions please call lead tech for that job; Owen ###-####. Phone #: ###-#### Internet Inspection Request from: Yolanda Morris called left correction notice, nec 356.26 there shall not be over 4 quarter bends in lfnc, 348.30 shall strap flex within 12" of termination point, 422.31 shall provide disconnect in sight of appliance or provide breaker lock-out, 300.4 conductors shall be protected from damage, 110.2 (B) listed equipment shall be installed per manufacturers instructins, gfci has open neutral, recpt has h&n reversed
|