Final | 2/5/2018 | 2/14/2018 | 2/14/2018 | P | PASS |
Tom Saunders
|
|
|
Please call ahead for access, inspection close a previoulsy expired permit - David Phone #: ###-####...corrections made...ok to final
|
Final | 1/25/2018 | 1/30/2018 | 2/6/2018 | A | FAIL |
Daryl DeGrange
|
|
|
Please call ahead for access, inspection close a previoulsy expired permit - David Phone #: ###-#### No answer/ mail box full
|
ELE-Aging Inspection | 1/18/2010 | 1/18/2010 | 1/20/2010 | | CANC |
Jack Frank
|
|
|
|
DOC - Permit Expired | 1/20/2010 | 1/20/2010 | 1/20/2010 | P | PASS |
Jack Frank
|
|
|
no activity
|
Final | 11/12/2008 | 11/13/2008 | 11/13/2008 | A | FAIL |
Jack Frank
|
|
|
Jeremy Phone #: ###-#### corr new violation shall not ID 6 or smaller neutral or equip grd, clearence for sub panel not done remove shelf, manufsctures breakers only
|
Final | 6/25/2008 | 6/25/2008 | 6/25/2008 | P | FAIL |
Jack Frank
|
|
|
Jeremy Phone #: ###-#### corr. called 110.26(F)(1) clearence for sub panel , 408.4 be specific, 300.12 terminate LFNC to p/s and remove romex too many bends in LFNC, use manufactures listed breakers only at p/s 314.20 box extension at outlet in cabinet wet bar
|
Electrical Rough-In | 4/11/2008 | 4/11/2008 | 4/11/2008 | P | PASS |
Jack Frank
|
|
|
Jeremy ; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok new basement
|