Final | 6/5/2008 | 6/6/2008 | 6/6/2008 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Surerus ok
|
Final | 5/20/2008 | 5/20/2008 | 5/20/2008 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Surerus 210.52(A) needs outlet for wall space between bath and closet doors, check clearence closet fixture if it is incandescent, 410.8 also needs service change for proper size house calcs out over 100 amp contr said called
|
Electrical Rough-In | 4/14/2008 | 4/15/2008 | 4/15/2008 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Dan Surerus called needs recept for wall space fixed panel of sider contr will install also need p/s calcs
|