Final | 10/24/2008 | 10/27/2008 | 10/27/2008 | A | PASS |
Pat Lass
|
|
|
shallan Phone #: ###-####
|
Final | 10/23/2008 | 10/24/2008 | 10/24/2008 | A | FAIL |
Pat Lass
|
|
|
shallan Phone #: ###-#### install in use cover, AFCI protect bedroom outlets, panel directory, closet not to have open bulbs.
|
Rough-In Permanent Service | 8/14/2008 | 8/15/2008 | 8/15/2008 | A | PASS |
Mike Kinnear
|
|
|
shallan Phone #: ###-#### p/s o/h reconnect ok note no ri needed
|
Electrical Rough-In | 8/11/2008 | 8/12/2008 | 8/12/2008 | P | PASS |
Bob Reichert
|
|
|
shallan Phone #: ###-#### ok to pour concrete encased electrode, ric ok, will call for p/s later
|
Electrical Rough-In | 8/6/2008 | 8/7/2008 | 8/7/2008 | A | CANC |
Bob Reichert
|
|
|
Shallan Phone #: ###-#### see conference
|
Conference | 8/7/2008 | 8/7/2008 | 8/7/2008 | A | DONE |
Bob Reichert
|
|
|
Shallan Phone #: ###-#### not ready for ri, conductors require stapling, boxes mounted, make-up, flush out boxes, 6" free conductor, talked about service and grounding and sub-panel and junction boxes, too many conductors thru hole to be fire stopped
|
Conference | 6/23/2008 | 6/24/2008 | 6/24/2008 | P | DONE |
Bob Reichert
|
|
|
Shallan Phone #: ###-#### reviewed general requirements regarding inspections, nec requirements, 1 1/4", stapling, circuits, free conductor length, box fill, stack-its, service clearances, what inspector may see at inspection time
|