Final | 7/7/2008 | 7/8/2008 | 7/8/2008 | A | PASS |
Jack Frank
|
|
|
Garage code for access is 4801 Phone #: ###-#### Internet Inspection Request from: Shawn Kelley called needs panel schedule to be specific ok
|
Final | 5/19/2008 | 5/20/2008 | 5/20/2008 | A | CANC |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Shawn Kelley wrong type inspection
|
Electrical Rough-In | 5/20/2008 | 5/20/2008 | 5/20/2008 | A | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Shawn Kelley ok cover ri
|
Electrical Rough-In | 5/16/2008 | 5/19/2008 | 5/19/2008 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Shawn Kelley called, left correction notice, nec 210.52(A)(1)&(2) receptacles shall be within 6' of wall space and walls over 2' shall have receptacle installed-see kitchen wall and room east of kitchen, 210.52(E) shall install receptacle at front of dwelling, 300.4(D) edge of nm cable shall be 1 1/4" from edge of framing member Note: minimum 13 rooms for room count
|
Permanent Service | 5/2/2008 | 5/5/2008 | 5/5/2008 | P | PASS |
Mike Kinnear
|
|
|
shawn Phone #: ###-#### p/s o/h n ok
|