ELE-Aging Inspection | 8/4/2010 | 8/4/2010 | 8/4/2010 | | DONE |
Bob Reichert
|
|
|
see doc expire
|
DOC - Permit Expired | 8/4/2010 | 8/4/2010 | 8/4/2010 | A | PASS |
Bob Reichert
|
|
|
no activity
|
ELE-Aging Inspection | 6/4/2010 | 6/4/2010 | 6/4/2010 | | DONE |
Bob Reichert
|
|
|
suc
|
ELE-Aging Inspection | 3/31/2010 | 4/1/2010 | 4/1/2010 | A | DONE |
Bob Reichert
|
|
|
looked at part of job, called contractor, he doesn't want to finish job because owner not paying contractors, observed open breaker openings in panel, no labelling at service, closet light violation, open ground in receptacle, mbr has open buried outlet, entry requires outlets, jetted tub requires access, lot of painting going on, so no access to kitchen area
|
Electrical Rough-In | 2/13/2009 | 2/13/2009 | 2/13/2009 | P | PASS |
Pat Lass
|
|
|
Daniel- call 30 mins prior to going Phone #: ###-#### basement R/I Ok
|
Permanent Service | 2/2/2009 | 2/2/2009 | 2/2/2009 | P | CANC |
Pat Lass
|
|
|
dan Note: please call 1/2 prior to inspection Phone #: ###-####
|
Electrical Rough-In | 2/2/2009 | 2/2/2009 | 2/2/2009 | P | PART |
Pat Lass
|
|
|
dan Note: please call 1/2 prior to inspection Phone #: ###-#### this was a conf. only
|
Electrical Rough-In | 1/30/2009 | 2/2/2009 | 2/2/2009 | A | NH |
Pat Lass
|
|
|
Daniel-please call prior to inspection so he can meet ya there Phone #: ###-#### called and left message
|
Permanent Service | 12/11/2008 | 12/11/2008 | 12/11/2008 | P | FAIL |
Pat Lass
|
|
|
daniel Phone #: ###-#### no main bonding jumpers, breakers too high, equipment ground not run with feed to panel, grounding electrode conductors not to be spliced in panel buss. modified cable connector used as chase niple, cable to follow surface closely in unfinished basement isolate neutrals in sub panel one sub panel too high to remove cover. ground metal boxes, 4 wire receptacle to be fed with 4 wires.
|
Electrical Rough-In | 12/11/2008 | 12/11/2008 | 12/11/2008 | P | PART |
Pat Lass
|
|
|
daniel Phone #: ###-#### main level ok
|
Permanent Service | 5/9/2008 | 5/14/2008 | 5/14/2008 | P | PASS |
Bob Reichert
|
|
|
daniel Note: late as possible please Phone #: ###-#### p/s u/g rec ok- NOTE; this is conditional reconnect, must call for inspection to verify 2nd panel, subpanel, etc. May require another outage.
|