Permit NumberELE08-01186
StatusExpired
Name ULTIMATE ELECTRIC LLC
Site Address 2900 N SHEFFIELD CT
Project Name 
Customer Number 
ePlanReview 
Description
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
ELE-Aging Inspection8/4/20108/4/20108/4/2010 DONE
DetailsBob Reichert
see doc expire
DOC - Permit Expired8/4/20108/4/20108/4/2010APASS
DetailsBob Reichert
no activity
ELE-Aging Inspection6/4/20106/4/20106/4/2010 DONE
DetailsBob Reichert
suc
ELE-Aging Inspection3/31/20104/1/20104/1/2010ADONE
DetailsBob Reichert
looked at part of job, called contractor, he doesn't want to finish job because owner not paying contractors, observed open breaker openings in panel, no labelling at service, closet light violation, open ground in receptacle, mbr has open buried outlet, entry requires outlets, jetted tub requires access, lot of painting going on, so no access to kitchen area
Electrical Rough-In2/13/20092/13/20092/13/2009PPASS
DetailsPat Lass
Daniel- call 30 mins prior to going Phone #: ###-####
basement R/I Ok
Permanent Service2/2/20092/2/20092/2/2009PCANC
DetailsPat Lass
dan Note: please call 1/2 prior to inspection Phone #: ###-####
Electrical Rough-In2/2/20092/2/20092/2/2009PPART
DetailsPat Lass
dan Note: please call 1/2 prior to inspection Phone #: ###-####
this was a conf. only
Electrical Rough-In1/30/20092/2/20092/2/2009ANH
DetailsPat Lass
Daniel-please call prior to inspection so he can meet ya there Phone #: ###-####
called and left message
Permanent Service12/11/200812/11/200812/11/2008PFAIL
DetailsPat Lass
daniel Phone #: ###-####
no main bonding jumpers, breakers too high, equipment ground not run with feed to panel, grounding electrode conductors not to be spliced in panel buss. modified cable connector used as chase niple, cable to follow surface closely in unfinished basement isolate neutrals in sub panel one sub panel too high to remove cover. ground metal boxes, 4 wire receptacle to be fed with 4 wires.
Electrical Rough-In12/11/200812/11/200812/11/2008PPART
DetailsPat Lass
daniel Phone #: ###-####
main level ok
Permanent Service5/9/20085/14/20085/14/2008PPASS
DetailsBob Reichert
daniel Note: late as possible please Phone #: ###-#### p/s u/g rec ok- NOTE; this is conditional reconnect, must call for inspection to verify 2nd panel, subpanel, etc. May require another outage.