ELE-Aging Inspection | 1/28/2010 | 1/29/2010 | 1/29/2010 | A | CANC |
Jack Frank
|
|
|
|
DOC - Permit Expired | 1/29/2010 | 1/29/2010 | 1/29/2010 | A | PASS |
Jack Frank
|
|
|
|
Permanent Service | 5/12/2008 | 5/13/2008 | 5/13/2008 | A | FAIL |
Bob Reichert
|
|
|
bucandi Phone #: ###-#### called, left correction notice on front fence, NEC 408.4 circuit directory shall be clear, concise, dierect, and explanatory, 312.5 all conductors entering enclosure shall have abrasion protection, 250.50 shall use water pipe for primary grounding electrode and augment with 2 ground rods
|