ELE-Aging Inspection | 8/4/2010 | 8/4/2010 | 8/4/2010 | | DONE |
Bob Reichert
|
|
|
see doc expire
|
DOC - Permit Expired | 8/4/2010 | 8/4/2010 | 8/4/2010 | A | PASS |
Bob Reichert
|
|
|
no activity
|
ELE-Aging Inspection | 6/4/2010 | 6/4/2010 | 6/8/2010 | | DONE |
Bob Reichert
|
|
|
suc
|
Final | 9/8/2009 | 9/8/2009 | 9/8/2009 | P | FAIL |
Doug A Poedy
|
|
|
barb - please call 1/2 hr prior Phone #: ###-####. NEC 110.3 B Instalation and use.
|
Electrical Rough-In | 5/28/2008 | 5/28/2008 | 5/28/2008 | P | PASS |
Pat Lass
|
|
|
tony Phone #: ###-####
|
Conference | 5/20/2008 | 5/20/2008 | 5/20/2008 | A | DONE |
Jack Frank
|
|
|
300.4 nail plates and 11/4" for cables, 210.52(A&B) required outlets for wall space new and old wall of kit and liv rm, shall not use SABC for micro wave D W disposal , only what code allows shall be on SABC, 250.140 shall use 4 wire for new oven, 314.16 box fill adjustible boxes in kit, called
|
Electrical Rough-In | 5/19/2008 | 5/20/2008 | 5/20/2008 | A | FAIL |
Jack Frank
|
|
|
tony - please call for access Phone #: see added conference
|