Permanent Service | 5/20/2008 | 5/20/2008 | 5/20/2008 | P | PART |
Jack Frank
|
|
|
###-#### - corey ###-#### office when finished p/s u/g rec. ok
|
Final | 5/20/2008 | 5/20/2008 | 5/20/2008 | P | PASS |
Jack Frank
|
|
|
###-#### - corey ###-#### office when finished ok
|
Final | 5/20/2008 | 5/20/2008 | 5/20/2008 | A | NR |
Jack Frank
|
|
|
Electrical questions call Cory @ ###-####. Upgraded 100 amp panel to 200 amp Phone #: ###-#### Internet Inspection Request from: Yolanda Morris called contr (cory) he will call for p/s when ready
|
Permanent Service | 5/19/2008 | 5/19/2008 | 5/19/2008 | P | FAIL |
Jack Frank
|
|
|
corr. called 110.26(F)(2) remove tree clearence for p/s, 250.92(A) bond steel raceway bottom of p/s meter side, 110.3, remove losd side feeder ser cable from meter side of service gear 310.16 shall protect #12 feeder to a/c at 20 amps not 30 check 4wire brach circuits for range abd dryer, remove old GEC you have a the new one did not have access to inside house could not check subpanel or grds or bonds to water
|
Electrical Rough-In | 5/19/2008 | 5/20/2008 | 5/19/2008 | A | CANC |
Jack Frank
|
|
|
blanca Phone #: ###-#### Inspection cancelled from web by: Yolanda Morris
|