Permit Information
Permit NumberELE08-01278
StatusFinaled
Name HARDLINE ELECTRIC
Site Address 2774 S KYLEE PL
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - New: New house with unfinished basement
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/5/20088/5/20088/5/2008PPASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Lynn Cable corrections made ok to final
Final8/3/20088/4/20088/4/2008AFAIL
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Lynn Cable called, left correction notice, NRC 210.52(C)(1) shall provide receptacle in wall counter space such that no point is over 24" from outlet, 210.52(A) shall provide receptacle in 2' wall space in bonus room and at top of stairs, 210.70(A)(3) shall provide lighting outlet for downstairs panel
Rough-In Permanent Service5/19/20085/19/20085/19/2008PPASS
DetailsBob Reichert
ready for re-inspection. Phone #: ###-#### Internet Inspection Request from: Lynn Cable corrections made, ric ok, p/s u/g n ok
Rough-In Permanent Service5/15/20085/16/20085/16/2008AFAIL
DetailsBob Reichert
unfished basement, thanks Phone #: ###-#### Internet Inspection Request from: Lynn Cable called, left correction notice, NEC 334.30 nm cable shall be secured within 12" of box, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing member, 110.12 (C) there shall be no damaged equipment-jacket of ser cable, 334.80 shall derate conductors where more than 2 nm cables pass thru framing that is to be fire or draft stopped, 334.30 shall secure nm cable within 12" of box, 210.52(A)(1)&(2) receptacles shall be spaced such that no point along wall line is over 6' from a receptacle, 210.8(A)(5) shall provide gfci in basement