Final | 6/16/2008 | 6/17/2008 | 6/17/2008 | A | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 6/16/2008 at 11:10:55 PM. Contact: ###-####. ok card signed
|
Final | 6/13/2008 | 6/13/2008 | 6/13/2008 | P | NR |
Jack Frank
|
|
|
Neil Phone #: ###-#### called left message
|
Electrical Rough-In | 6/9/2008 | 6/10/2008 | 6/10/2008 | A | PASS |
Pat Lass
|
|
|
Neil Phone #: ###-#### plans on site no esc permit
|
Final | 6/9/2008 | 6/9/2008 | 6/9/2008 | P | FAIL |
Bob Reichert
|
|
|
Neil Phone #: ###-#### called, left corredction notice, NEC 330.30(B) mc cable shall be secured within 12" of termination, 725.3(B) abandoned class 2, 3, pltc cable shall be removed, no esc
|
Electrical Rough-In | 5/20/2008 | 5/20/2008 | 5/20/2008 | P | PART |
Jack Frank
|
|
|
Neal ###-####///please call for access info walls and u/g ok
|