Final | 7/9/2008 | 7/9/2008 | 7/9/2008 | P | PASS |
Jack Frank
|
|
|
CONTACT: LEON SHEFFIELD Phone #: ###-#### Internet Inspection Request from: Deb ok survey posted T310.16 50 amp max breakers for #8 copper
|
Final | 7/3/2008 | 7/7/2008 | 7/7/2008 | A | FAIL |
Bob Reichert
|
|
|
contact: Leon Sheffield Phone #: ###-#### Internet Inspection Request from: Deb Gooden called, left message, ground rods ok, no power to check, NEC 410.15(B) shall provide raintight handholes at poles, 408.4 shall complete circuit directory, 230.24 gec and grounded conductor shall be connected
|
Final | 7/2/2008 | 7/3/2008 | 7/3/2008 | A | FAIL |
Jack Frank
|
|
|
Contact Leon. Phone #: ###-#### Internet Inspection Request from: Shelli Daylong corr 250.32 shall install grd rods at all 4 power pedestals called
|
Electrical Rough-In | 5/29/2008 | 5/30/2008 | 5/30/2008 | A | PASS |
Bob Reichert
|
|
|
CONTACT: LEON SHEFFIELD - UNDERGROUND INSPECTION PLEASE Phone #: ###-#### Internet Inspection Request from: Deb Gooden u/g ok to cover, told contractor to tie esc permit to electrical if available
|