Final | 8/21/2008 | 8/22/2008 | 8/22/2008 | A | PASS |
Bob Reichert
|
|
|
mike Phone #: ###-#### met contractor, left survey, NEC 210.70 shall provide lighting outlet at garage man door, ok to final, no esc this project
|
Electrical Rough-In | 6/20/2008 | 6/23/2008 | 6/23/2008 | P | PASS |
Bob Reichert
|
|
|
Mike Phone #: ###-#### corrections made, ric ok, no esc this project, walls opened, met contractor
|
Electrical Rough-In | 6/11/2008 | 6/11/2008 | 6/11/2008 | P | FAIL |
Jack Frank
|
|
|
Mike- call 20 min prior to going Phone #: ###-#### contr did not remove all the sheetrock that I told him to remove , where it was removed I found violations 300.4 11/4" for cables parallel to framing members, also NMB cables not stapled within 8" of boxes
|
Conference | 5/30/2008 | 5/30/2008 | 5/30/2008 | P | DONE |
Jack Frank
|
|
|
mike ###-#### corr posted double permit fee due work done without permit and covered without inspection shall remove all sheetrock, all wiring shall meet current 2005 N E C meet contractor at site per J Schmer instrutions will sent Jim a investigation report
|