Final | 7/1/2008 | 7/2/2008 | 7/2/2008 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Lloyd Looney corrections made, ok to final, no card to sign, no esc this project
|
Final | 6/25/2008 | 6/26/2008 | 6/26/2008 | A | FAIL |
Bob Reichert
|
|
|
Need final in Cole-Mar TI space Phone #: ###-#### Internet Inspection Request from: Lloyd Looney called, left correction notice, BCC no violations shall be retained, receptacles shall operate, NEC 408.4 circuit directories shall be clear, concise, complete,etc, 406.4 receptacles shall be securely mounted, 406.4(D) shall install receptacle face plates, 314.25 boxes shall have covers installed, 314.27 shall provide boxes for lighting outlets, 400.8 cord shall not be concealed in ceilings, no esc this project
|
Electrical Rough-In | 6/2/2008 | 6/3/2008 | 6/3/2008 | A | PASS |
Bob Reichert
|
|
|
new new store front rough inspection suite 100, 154, 158 (all are being made into one suite) Phone #: ###-#### Internet Inspection Request from: Lloyd Looney store fronts only ok to cover for suites listed, no esc
|