Final | 6/16/2008 | 6/16/2008 | 6/16/2008 | P | PASS |
Bob Reichert
|
|
|
Final inspection. Kelly Tarter ###-#### Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson corrections made, ok to final, no esc
|
Final | 6/13/2008 | 6/13/2008 | 6/13/2008 | P | FAIL |
Bob Reichert
|
|
|
Kelly Tarter ###-#### Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson called, left correction notice,NEC 408.4 shall provide circuit directories and be clear and concise, 312.5 shall provide abrasion protection for all conductors entering enclosures, 352.30(A) rnc shall be securely supported within 3' of termination,250.24(A) grounding electrode conductor shall be connected to grounded conductor at service, 250.28 shall provide main bonding jumper, 250.53(G) grounding electrode conductor shall be attached to rod, 406.8(B) shall use in-use type receptacle cover, 356.30 lfnc shall be supported within 12" of termination, 110.3(B) listed equipment shall be installed per instructions included, no esc
|
Final | 6/11/2008 | 6/12/2008 | 6/12/2008 | A | CANC |
Mike Kinnear
|
|
|
Final Inspection. Kelly Tarter Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson wrong type inspection
|
Conference | 6/12/2008 | 6/12/2008 | 6/12/2008 | A | DONE |
Mike Kinnear
|
|
|
Final Inspection. Kelly Tarter Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson t/w electrcian needs 2 ground rods for service seperater structure, pvc needs to be straped every 3ft. ok cover under ground conduit
|