Final | 10/15/2008 | 10/16/2008 | 10/16/2008 | A | PASS |
Jack Frank
|
|
|
Final Inspection. Please call Rick Sendra @ ###-#### prior to inspection in order to gain entrance. Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson ok survey posted 314.43 screws not allowed in plastic box kit. left of sink, 210.8 gfci outlets 6ft of laundry sink
|
Final | 10/8/2008 | 10/9/2008 | 10/9/2008 | A | FAIL |
Jack Frank
|
|
|
Final Inspection. Please call Rick Sendra @ ###-#### to gain entry 30 minutes prior to inspection. Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson met contr corr posted 210.52(A) outlet spacing sewing rm and living rm by pocket door downstairs 210.52(C) outlet spacing left of kit sink, 410.8 fixture clearwence downstairs bed rm closet, 210.8 gfci not working laundry rm and mech. rm
|
Final | 10/7/2008 | 10/8/2008 | 10/8/2008 | A | CANC |
Bob Reichert
|
|
|
Final Inspection. Please call Rick Sendra @ ###-#### 30 minutes prior to inspection to gain entry. Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson talked with contractor, will reschedule for am tomorrow
|
Electrical Rough-In | 7/10/2008 | 7/10/2008 | 7/10/2008 | P | PASS |
William E Thomas
|
|
|
R.I. Reinspect. Bob J. ###-#### Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson . .1. ri ok. . .
|
Permanent Service | 7/10/2008 | 7/10/2008 | 7/10/2008 | P | PASS |
William E Thomas
|
|
|
R.I. Reinspect. Bob J. ###-#### Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson . .1. p/s u/g n ok. . .
|
Permanent Service | 7/7/2008 | 7/8/2008 | 7/8/2008 | P | FAIL |
Jack Frank
|
|
|
Permanent Service inspection. Bob J. Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson see r/i request correction
|
Electrical Rough-In | 7/7/2008 | 7/8/2008 | 7/8/2008 | P | FAIL |
Jack Frank
|
|
|
Rough In inspection. Bob J. Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson corr met contr. 210.52(A) needs outlets 1 in NW bedrm 1 in kit left of pantry door, 300.4 nail plates and 11/4" cables parallel, 300.14 short wires at boxes, 334.23 cables 6ft of attic access, 110.26(F)(2) remove low voltage from below p/s
|
Electrical Rough-In | 6/27/2008 | 6/30/2008 | 6/30/2008 | P | FAIL |
Jack Frank
|
|
|
Basement and service inspection. Bob Johnston ###-#### Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson corr box fill screws in plastic boxes, 14 AWG on 20 circuit, vacuum outlets, needs bushings for SER
|
Electrical Rough-In | 6/17/2008 | 6/17/2008 | 6/17/2008 | P | PART |
Pat Lass
|
|
|
Rough inspection soffits. Please call Rick Sendra @ ###-#### Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson sofits ok
|