Final | 10/27/2008 | 10/28/2008 | 10/28/2008 | P | PASS |
Jack Frank
|
|
|
BOB Phone #: ###-#### ok no card
|
Electrical Rough-In | 10/16/2008 | 10/17/2008 | 10/17/2008 | P | PART |
Jack Frank
|
|
|
Scheduled via mobile device. Phone #: 7246714 Note: r/i customer service area SW corner of bld grid ceiling ok
|
Electrical Rough-In | 9/25/2008 | 9/26/2008 | 9/26/2008 | A | PART |
Jack Frank
|
|
|
bob - underground - meat and seafood dept. Phone #: ###-#### ok
|
Electrical Rough-In | 9/22/2008 | 9/23/2008 | 9/23/2008 | P | PART |
Jack Frank
|
|
|
bob Note: bakery, ceiling, and meat ceiling Phone #: ###-#### ok
|
Electrical Rough-In | 8/8/2008 | 8/11/2008 | 8/11/2008 | P | PART |
Jack Frank
|
|
|
Bob Phone #: ###-#### u/g between deli and starbucks ok
|
Electrical Rough-In | 8/5/2008 | 8/6/2008 | 8/6/2008 | P | PART |
Jack Frank
|
|
|
Bob- call 1 hr prior to going Phone #: ###-#### coffee equip ok
|
Electrical Rough-In | 7/31/2008 | 8/1/2008 | 8/1/2008 | P | FAIL |
Jack Frank
|
|
|
Bob- please call 1 hr prior to going Phone #: ###-#### corr., met contr NEC 110.2 equipment labeled but does not say what it is, and too many violations to note, some of the violations are box fill boxes not grounded, over 360 degrees of bends in raceways, needs 6" free length of conductors and strap within 12" of boxes for cables and flex note partial corr only this is for starbucks
|
Electrical Rough-In | 7/16/2008 | 7/16/2008 | 7/16/2008 | P | PASS |
William E Thomas
|
|
|
Bob- call 1 hr prior to going Phone #: ###-#### . .1. ok to cover. . .
|
Electrical Rough-In | 7/15/2008 | 7/16/2008 | 7/16/2008 | A | NH |
William E Thomas
|
|
|
bob Note: underground/also note to meet/or call with contact 60 minutes prior - only 20 ft trench in the phar/by starbucks coffee Phone #: ###-#### . .1. not accessable. .. .
|