Permit Information
Permit NumberELE08-01787
StatusFinaled
Name S & J ELECTRIC
Site Address 10700 W USTICK RD
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - Addition: Albertsons 161 remodel
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/13/200811/14/200811/14/2008APASS
DetailsJack Frank
Kyle Phone #: ###-#### ok card signed
Final10/31/200811/3/200811/3/2008PFAIL
DetailsJack Frank
kyle Phone #: ###-#### 200.6&7 shall not use ungrounded conductor in MC cable as neutral, correction posted on BLD permit no violation to be retained 410.62(C) cord fed fixtures shall be fed with recept and cord cap or use factory canopy old work done without permit or inspection
Electrical Rough-In10/2/200810/2/200810/2/2008APART
DetailsJack Frank
Scheduled by a contractor via Hello! on 10/2/2008 at 7:06:11 AM. Contact: ###-####. 3 outlet in deli ok
Electrical Rough-In9/26/20089/26/20089/26/2008PPART
DetailsJack Frank
kyle - underground Phone #: ###-#### ok
Electrical Rough-In9/25/20089/25/20089/25/2008APART
DetailsPat Lass
Scheduled by a contractor via Hello! on 9/25/2008 at 7:03:38 AM. Contact: ###-####.
old pharmacy ceiling and chip machine ok
Electrical Rough-In9/5/20089/5/20089/5/2008PPART
DetailsJack Frank
Scheduled by a contractor via Hello! on 9/5/2008 at 6:36:16 AM. Contact: ###-####. starbucks and pharmacy ok
Electrical Rough-In9/4/20089/4/20089/4/2008PFAIL
DetailsJack Frank
Lance- early PM Phone #: ###-#### called asked for lance person said I have the wrong number
Electrical Rough-In9/3/20089/3/20089/3/2008PFAIL
DetailsJack Frank
Shane- cabinet rough-in pharmacy Phone #: ###-#### corr talked with contr. pharmacy, box fill, starbucks box fill secure all cables and flex, grd all boxes, over 360 degrees of bends in flex
Electrical Rough-In8/28/20088/28/20088/28/2008APART
DetailsJack Frank
Scheduled by a contractor via Hello! on 8/28/2008 at 6:47:23 AM. Contact: ###-####.pharmacy ceiling ok told contr about listed cabinets boxes too small, and bond new HW pipes
Electrical Rough-In8/27/20088/27/20088/27/2008AFAIL
DetailsJack Frank
Scheduled by a contractor via Hello! on 8/27/2008 at 7:10:39 AM. Contact: ###-####. called left message do not know what they want inspected contr has not called me back with info
Electrical Rough-In8/21/20088/22/20088/22/2008APART
DetailsJack Frank
kyle Phone #: ###-#### walls and hard ceilings pharmacy corr. posted for low voltage removed abandoned cables, and support cables
Electrical Rough-In8/11/20088/11/20088/11/2008PPART
DetailsJack Frank
Lance-###-#### Phone #: ###-#### 1 outlet in wall by bank
Rough-In Permanent Service7/22/20087/23/20087/23/2008PPASS
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 7/22/2008 at 11:53:37 PM. Contact: ###-####. ok wires for service change p/s u/g reconnect ok
Electrical Rough-In7/20/20087/21/20087/21/2008PPASS
DetailsMike Kinnear
Scheduled by a contractor via Hello! on 7/20/2008 at 10:07:12 PM. Contact: ###-####. ok cover under slab conduit produce area
Electrical Rough-In7/17/20087/18/20087/18/2008PPART
DetailsBob Reichert
Lance Phone #: ###-#### corrections made, walls only ok to cover anop
Electrical Rough-In7/16/20087/17/20087/17/2008PFAIL
DetailsBob Reichert
Scheduled by a contractor via Hello! on 7/16/2008 at 9:47:22 PM. Contact: ###-####. called, left message, left correction notice, NEC 330.30 mc cable shall be secured within 12" of box, 330.17 mc cable shall be protected in accordance with 300.4(A), (C), & (D) where installed through framing members (1/14"), BCC mc cable shall not be run in valley of steel studs