Final | 11/13/2008 | 11/14/2008 | 11/14/2008 | A | PASS |
Jack Frank
|
|
|
Kyle Phone #: ###-#### ok card signed
|
Final | 10/31/2008 | 11/3/2008 | 11/3/2008 | P | FAIL |
Jack Frank
|
|
|
kyle Phone #: ###-#### 200.6&7 shall not use ungrounded conductor in MC cable as neutral, correction posted on BLD permit no violation to be retained 410.62(C) cord fed fixtures shall be fed with recept and cord cap or use factory canopy old work done without permit or inspection
|
Electrical Rough-In | 10/2/2008 | 10/2/2008 | 10/2/2008 | A | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 10/2/2008 at 7:06:11 AM. Contact: ###-####. 3 outlet in deli ok
|
Electrical Rough-In | 9/26/2008 | 9/26/2008 | 9/26/2008 | P | PART |
Jack Frank
|
|
|
kyle - underground Phone #: ###-#### ok
|
Electrical Rough-In | 9/25/2008 | 9/25/2008 | 9/25/2008 | A | PART |
Pat Lass
|
|
|
Scheduled by a contractor via Hello! on 9/25/2008 at 7:03:38 AM. Contact: ###-####. old pharmacy ceiling and chip machine ok
|
Electrical Rough-In | 9/5/2008 | 9/5/2008 | 9/5/2008 | P | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 9/5/2008 at 6:36:16 AM. Contact: ###-####. starbucks and pharmacy ok
|
Electrical Rough-In | 9/4/2008 | 9/4/2008 | 9/4/2008 | P | FAIL |
Jack Frank
|
|
|
Lance- early PM Phone #: ###-#### called asked for lance person said I have the wrong number
|
Electrical Rough-In | 9/3/2008 | 9/3/2008 | 9/3/2008 | P | FAIL |
Jack Frank
|
|
|
Shane- cabinet rough-in pharmacy Phone #: ###-#### corr talked with contr. pharmacy, box fill, starbucks box fill secure all cables and flex, grd all boxes, over 360 degrees of bends in flex
|
Electrical Rough-In | 8/28/2008 | 8/28/2008 | 8/28/2008 | A | PART |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 8/28/2008 at 6:47:23 AM. Contact: ###-####.pharmacy ceiling ok told contr about listed cabinets boxes too small, and bond new HW pipes
|
Electrical Rough-In | 8/27/2008 | 8/27/2008 | 8/27/2008 | A | FAIL |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 8/27/2008 at 7:10:39 AM. Contact: ###-####. called left message do not know what they want inspected contr has not called me back with info
|
Electrical Rough-In | 8/21/2008 | 8/22/2008 | 8/22/2008 | A | PART |
Jack Frank
|
|
|
kyle Phone #: ###-#### walls and hard ceilings pharmacy corr. posted for low voltage removed abandoned cables, and support cables
|
Electrical Rough-In | 8/11/2008 | 8/11/2008 | 8/11/2008 | P | PART |
Jack Frank
|
|
|
Lance-###-#### Phone #: ###-#### 1 outlet in wall by bank
|
Rough-In Permanent Service | 7/22/2008 | 7/23/2008 | 7/23/2008 | P | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 7/22/2008 at 11:53:37 PM. Contact: ###-####. ok wires for service change p/s u/g reconnect ok
|
Electrical Rough-In | 7/20/2008 | 7/21/2008 | 7/21/2008 | P | PASS |
Mike Kinnear
|
|
|
Scheduled by a contractor via Hello! on 7/20/2008 at 10:07:12 PM. Contact: ###-####. ok cover under slab conduit produce area
|
Electrical Rough-In | 7/17/2008 | 7/18/2008 | 7/18/2008 | P | PART |
Bob Reichert
|
|
|
Lance Phone #: ###-#### corrections made, walls only ok to cover anop
|
Electrical Rough-In | 7/16/2008 | 7/17/2008 | 7/17/2008 | P | FAIL |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 7/16/2008 at 9:47:22 PM. Contact: ###-####. called, left message, left correction notice, NEC 330.30 mc cable shall be secured within 12" of box, 330.17 mc cable shall be protected in accordance with 300.4(A), (C), & (D) where installed through framing members (1/14"), BCC mc cable shall not be run in valley of steel studs
|