Final | 8/8/2008 | 8/11/2008 | 8/11/2008 | A | PASS |
Jack Frank
|
|
|
reinspection Phone #: ###-#### Internet Inspection Request from: Jari Rivers ok
|
Final | 8/4/2008 | 8/5/2008 | 8/5/2008 | A | FAIL |
Jack Frank
|
|
|
Internet Inspection Request from: Jari Rivers corr 352.10(F) shall use schedule 80 all exposed RNC, 250.119 shall not ID #6 equip grd shall be green, 110.14(A) equip grd bus loose, 680.22(A)(3) needs gfci recept 10 ft 20 ft for spa
|
Final | 7/31/2008 | 7/31/2008 | 7/31/2008 | P | NH |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Jari Rivers no access dog
|
Electrical Rough-In | 7/2/2008 | 7/3/2008 | 7/3/2008 | A | PART |
Jack Frank
|
|
|
ug conduit inspection for hot tub Phone #: ###-#### Internet Inspection Request from: Jari Rivers ok
|