Final | 8/11/2008 | 8/11/2008 | 8/11/2008 | P | PASS |
Jack Frank
|
|
|
Please call Don Burney w 1/2 hr notice for access at ###-####. Thanks, Andrea. Phone #: ###-#### x0000 Internet Inspection Request from: Andrea Creek ok
|
Electrical Rough-In | 7/16/2008 | 7/16/2008 | 7/16/2008 | P | PASS |
Mike Kinnear
|
|
|
Please call Jeff at ###-#### w/ 1/2 hr notice so he can meet you there. Thanks. Phone #: ###-#### x0000 Internet Inspection Request from: Andrea Creek ok cover ri note survey bathrm outlets shall be on 20amp curc. no esc permit in project
|
Permanent Service | 7/9/2008 | 7/9/2008 | 7/9/2008 | P | PASS |
Jack Frank
|
|
|
Please make as late in day as you can and call Jeff when on way at ###-#### w/ 1/2hr notice for access. Thanks, Andrea. Phone #: ###-#### x0000 Internet Inspection Request from: Andrea Creek contr will install guy kit , and bond water p/s o/h rec. ok
|
Permanent Service | 7/8/2008 | 7/8/2008 | 7/8/2008 | P | FAIL |
Bob Reichert
|
|
|
If any questions please call Jeff Creek at ###-####. Thanks, Andrea. Phone #: ###-#### x0000 Internet Inspection Request from: Andrea Creek called left message, left correction notice, NEC 250.52(A)(3) concrete encased electrode shall be min. 20' bare copper not smaller than #4 awg surrounded by at least 2" concrete, 310.11(B) service entrance cable shall bear "sunlight resistant" marking,BCC all u/g shall be inspected before cover
|