Final | 7/24/2008 | 7/28/2008 | 7/28/2008 | P | PASS |
Bob Reichert
|
|
|
Rough in new circuit from existing electrical panel,20amp breaker & whip Phone #: ###-#### Internet Inspection Request from: Yolanda Morris called, corrections made, ok to final
|
Electrical Rough-In | 7/8/2008 | 7/11/2008 | 7/11/2008 | P | FAIL |
Jack Frank
|
|
|
YOU MUST CALL JANET AT ###-#### 15-20 MINUTES BEFORE YOU GO, SHE WILL MEET YOU THERE. ANY QUESTIONS ABOUT WORK PLEASE CALL TED AT ###-####. THANKS Phone #: ###-#### Internet Inspection Request from: Yolanda Morris 356.26 over 360 degrees of bends in LFNC,440.14 needs dissconnect in sight of a/c unit, 406.8&11 needs WR and tamperproof recept for added outlet, 408.4 label panel be specific, 200.6 shall not use #10 white as phase conductor called
|