Final | 7/28/2008 | 7/28/2008 | 7/28/2008 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA ok to final
|
Electrical Rough-In | 7/16/2008 | 7/16/2008 | 7/16/2008 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA corrections made, ric ok
|
Electrical Rough-In | 7/14/2008 | 7/15/2008 | 7/15/2008 | A | FAIL |
Pat Lass
|
|
|
Phone #: ###-#### Internet Inspection Request from: HARVEY REYNA 386.60 Grounding Surface metal raceway enclosures providing a transition from other wiring methods shall have a means for connecting an equipment grounding conductor. 386.100 Construction Surface metal raceways and their elbows, couplings, and similar fittings shall be designed so that the sections can be electrically and mechanically coupled together and installed without subjecting the wires to abrasion. 250.148 Continuity and Attachment of Equipment Grounding Conductors to Boxes. (A) Metal Boxes. A connection shall be made between the one or more equipment grounding conductors and a metal box 314.16 Number of Conductors in Outlet, Device, and Junction Boxes, and Conduit Bodies. Boxes and conduit bodies shall be of sufficient size to provide free space for all enclosed conductors. 6 #14 max in 1 7/8” deep handi box. 210.52 Dwelling Unit Receptacle Outlets. (A) General Provisions. In every kitchen, family room, dining room, living room, parlor, library, den, sunroom, bedroom, recreation room, or similar room or area of dwelling units, receptacle outlets shall be installed in accordance with the general provisions specified in 210.52(A)(1) through (A)(3). Within 6 ft. of door openings.
|