Final | 10/13/2008 | 10/13/2008 | 10/13/2008 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack ok
|
Final | 9/19/2008 | 9/22/2008 | 9/22/2008 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack called left message, corr. BCC ans 110.2 listing of equip. , electric gates, field evaluated sticker no record of it to J Schmer, looks like someone just stuck the sticker on equip, 314.3 metallic raceway and fitting not allowed at sprinkler time clock
|
Permanent Service | 8/25/2008 | 8/25/2008 | 8/25/2008 | P | PASS |
Bob Reichert
|
|
|
AIC from Idaho Power is 3162, contact Steve Petrie @ ###-#### Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack corrections made, p/s u/g n ok
|
Permanent Service | 8/20/2008 | 8/21/2008 | 8/21/2008 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack met contractor,, left correction notice, NEC 250.94 shall provide intersystem bonding termination, 250.92(B) shall use listed devices for bonding raceway at service, 110.3(B) listed equipment shall be installed in accordance with instructions in labelling- contactors must not have over 5kaic available
|
Electrical Rough-In | 7/21/2008 | 7/22/2008 | 7/22/2008 | P | PASS |
Bob Reichert
|
|
|
ug conduit Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack ok to cover u/g
|