ELE-Aging Inspection | 2/24/2010 | 2/24/2010 | 3/1/2010 | | CANC |
Jack Frank
|
|
|
|
Final | 3/1/2010 | 3/1/2010 | 3/1/2010 | A | PASS |
Jack Frank
|
|
|
|
Permanent Service | 9/8/2008 | 9/8/2008 | 9/8/2008 | P | PASS |
Bob Reichert
|
|
|
ROBERT Phone #: ###-#### p/s o/h rec ok, no esc this project
|
Permanent Service | 7/29/2008 | 7/29/2008 | 7/29/2008 | P | FAIL |
Bob Reichert
|
|
|
Robert Phone #: ###-#### talked with owner, left correction notice, NEC 240.4 shall use overcurrent protection for rating of cord conductors i.e. 50a in service panel,408.4 shall provide circuit directory, 552.43(B) shall provide strain relief for cord to prevent strain to terminals in panel, 230.24(A) shall provide 8' clearance for service conductors over roof, 110.13 the panel shall be securely mounted (wall is loose), 110.14 all electrical connections shall be made, no esc this project
|