Final | 12/10/2008 | 12/10/2008 | 12/10/2008 | P | PASS |
Bob Reichert
|
|
|
garage code 4548 Phone #: ###-#### Internet Inspection Request from: Therrin Robertson ok to final
|
Rough-In Permanent Service | 7/31/2008 | 7/31/2008 | 7/31/2008 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson corrections made, ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 7/29/2008 | 7/30/2008 | 7/30/2008 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called corr. 312.5 needs connectors for cables at panel, 210.52(B)(2) remove range hood from SABC, 362.30 strap ENT within 3ft of panel, B C C install boxes for pendant lights above island counter
|