Final | 10/2/2008 | 10/3/2008 | 10/3/2008 | A | PASS |
Bob Reichert
|
|
|
Garage code 1234 Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called, left survey, NEC 110.26(F)(2) no equipment shall be in dedicated space below panel, ok to final
|
Final | 9/30/2008 | 10/1/2008 | 10/1/2008 | A | NH |
Bob Reichert
|
|
|
garage code 4548 Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called contractor and also lead man, code doesn't work, key doesn't work, told to recall when can get in, fee due
|
Rough-In Permanent Service | 8/26/2008 | 8/26/2008 | 8/26/2008 | A | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called contractor, gave correct address and told him to call for inspection, this one has been done
|
Rough-In Permanent Service | 8/19/2008 | 8/19/2008 | 8/19/2008 | P | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called, left message, this job already done
|
Rough-In Permanent Service | 7/31/2008 | 7/31/2008 | 7/31/2008 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson corrections made, ric ok, p/s u/g n ok
|
Rough-In Permanent Service | 7/29/2008 | 7/30/2008 | 7/30/2008 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called corr. 21052(B)(2) range dood shall not be on SABC, 312.5 needs connectors for cables at panel 362.30 strap ENT 3ft of panels, B.C.C. install boxes for pendant lights over island counter
|