Permit Information
Permit NumberELE08-02167
StatusFinaled
Name NORTHWEST ELECTRICAL
Site Address 7557 W USTICK RD
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - New: New Library
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Electrical Rough-In6/16/20096/18/20096/18/2009APASS
DetailsJack Frank
Installation of stickers on light fixtures. Phone #: ###-#### Internet Inspection Request from: Mark Sessions ok u/l labels installed
Final6/18/20096/18/20096/18/2009APASS
DetailsJack Frank
Installation of stickers on light fixtures. Phone #: ###-#### Internet Inspection Request from: Mark Sessions ok card signed
Conference6/9/20096/9/20096/9/2009PDONE
DetailsBob Reichert
met 412 and 315 to observe cord violation thru ceiling, saw the contractors resolution, 315 signed t/o card
Final6/9/20096/9/20096/9/2009PPART
DetailsJack Frank
t/o ok card signed cords above ceiling is being addressed and violation corrected, still needs UL listeng for fixtures damp location on roof
Final6/4/20096/5/20096/5/2009PFAIL
DetailsJack Frank
I can also be reached at ###-####. Phone #: ###-#### Internet Inspection Request from: andy eckhart 250.8 &110.3(B) use manufactures listed equip grd bus roof switch, fixtures on roof listed for dry location only, 400.8 cords not allowed in raceway blinds
Electrical Rough-In5/4/20095/5/20095/5/2009APASS
DetailsJack Frank
Grid ceiling in South East corner of building Phone #: ###-#### Internet Inspection Request from: andy eckhart ok corr no cords allowed above ceiling, 400.7&8 cords for blinds
Electrical Rough-In5/1/20095/1/20095/1/2009PPART
DetailsBob Reichert
ceiling inspection//Andy ###-#### ok to cover 3 north east ceilings only
Electrical Rough-In4/22/20094/22/20094/22/2009PPART
DetailsJack Frank
andy Phone #: ###-#### center and west ceilings ok
Electrical Rough-In4/16/20094/16/20094/16/2009PPART
DetailsJack Frank
Andy Phone #: ###-#### partial for north and south wood ceilings ok
Electrical Rough-In4/9/20094/10/20094/10/2009APART
DetailsJack Frank
andy Phone #: ###-#### north and east corner ok building ceiling ok only still needs to meet 300.4 (E) for other areas, also 250.122 (B) for pole lights size of equip grd
Electrical Rough-In4/8/20094/8/20094/8/2009PCANC
DetailsBob Reichert
Request conference to discuss rough in. please call 919 3059 Phone #: ###-#### Internet Inspection Request from: Mark Sessions talked to contractor in notes and also contractor for permit number, neither wanted inspection or conference, or why request made. Ok to cancel- no esc for this
Electrical Rough-In4/7/20094/7/20094/7/2009PFAIL
DetailsJack Frank
Ceiling Phone #: ###-#### correction met contr 300.4(E) shall provide 11/2" or RMC, IMC for conduit at roof decking
Electrical Rough-In4/6/20094/6/20094/6/2009PPART
DetailsBob Reichert
Late Afternoon inspection for ceiling area where wood hard lid is being installed. Phone #: ###-#### Internet Inspection Request from: Mark Sessions ok to cover wood framed ceiling north and east 1/2 only
Permanent Service3/27/20093/30/20093/30/2009APASS
DetailsJack Frank
andy Phone #: ###-#### p/s u/g new ok
Permanent Service3/30/20093/30/20093/30/2009AFAIL
DetailsJack Frank
andy Phone #: ###-#### met contr needs to bond CT can will stop back later
Electrical Rough-In3/25/20093/25/20093/25/2009PPASS
DetailsJack Frank
Andy Phone #: ###-#### u/g for p/s ok
Electrical Rough-In3/19/20093/20/20093/20/2009APART
DetailsJack Frank
Please meet with Andy to discuss conduit route from CT can to switchgear. Phone #: ###-#### Internet Inspection Request from: Mark Sessions u/g for outside light west side of bld north to ustick
Conference3/13/20093/13/20093/13/2009ADONE
DetailsJack Frank
conference with engineer, on service entrance conductors, and manufactures instruction
Conference3/11/20093/11/20093/11/2009PDONE
DetailsJack Frank
p/s fail 110.3(B) manufacture's instructions, service entrance conductors shall enter main breaker section
Permanent Service3/10/20093/11/20093/11/2009APART
DetailsJack Frank
Andy Phone #: ###-#### no p/s conference only
Permanent Service3/3/20093/4/20093/4/2009ACANC
DetailsBob Reichert
andy Phone #: ###-#### talked to contractor, told to show 315 changed items, couldn't find way to get in, contractor didn't answer phone while there
Permanent Service2/27/20093/2/20093/2/2009APASS
DetailsJack Frank
andy Phone #: ###-#### needs 3/0 for GEC and bonds p/s u/g new ok
Electrical Rough-In2/19/20092/20/20092/20/2009PPART
DetailsJack Frank
andy Phone #: ###-#### hard ceilings in 2 restrms, and 2 small hard ceiling areas anop
Electrical Rough-In2/10/20092/10/20092/10/2009PPART
DetailsJack Frank
Andy Phone #: ###-#### rest rm walls and ceilings , and hard ceiling south anop
Electrical Rough-In1/21/20091/22/20091/22/2009PPART
DetailsJack Frank
andy Phone #: ###-#### east end walls ok
Electrical Rough-In1/8/20091/9/20091/9/2009PPART
DetailsJack Frank
Soffits Phone #: ###-#### Internet Inspection Request from: Mark Sessions
outside soffits, and west end office area walls ok
ELE-Aging Inspection12/25/200812/25/200812/26/2008 PART
DetailsJack Frank
wsuc
Electrical Rough-In10/21/200810/22/200810/22/2008APART
DetailsJack Frank
Site rough in conduits located on N.E. side of building. Phone #: ###-#### Internet Inspection Request from: Mark Sessions
u/g ok east side parking and planters
Electrical Rough-In9/24/20089/24/20089/24/2008PPART
DetailsJack Frank
Contact is Andy. Please inspect underslab electrical. Phone #: ###-#### Internet Inspection Request from: David Bonner
all u/g inside of building ok
Electrical Rough-In9/10/20089/11/20089/11/2008APART
DetailsJack Frank
Contact is Jason. Please inspect underground electrical. Phone #: ###-#### Internet Inspection Request from: David Bonner u/g feeders ok