Permit Information
Permit NumberELE08-02208
StatusFinaled
Name NORTHWEST ELECTRICAL
Site Address 1072 N LIBERTY ST
Project Name 
Customer Number 
ePlanReview 
Description
Electrical Permit - New: Core and shell
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/13/20095/14/20095/14/2009APASS
DetailsBob Reichert
jason Phone #: ###-#### corrections made, ok to final, signed structural card
Electrical Rough-In5/11/20095/11/20095/12/2009PPART
DetailsJack Frank
Jason Phone #: ###-#### entry ceiling ok some support needed contr will correct
Conference5/12/20095/12/20095/12/2009ADONE
DetailsJack Frank
Jason Phone #: ###-####-wall talked with contr. about ID of different voltages, phases and neutral, grding of separately derived systems
Final5/8/20095/8/20095/8/2009PPART
DetailsBob Reichert
Jason Phone #: ###-#### 1st floor ok except main entry requires ceiling inspection , told to remove tiles and support cables, they will check 3rd floor and recall if all corrections made
Final4/29/20094/29/20094/29/2009PFAIL
DetailsBob Reichert
Tom Phone #: ###-#### met contractor for roof top only, left correction notice, NEC 110.26(A)(2) shall provide at least 90 degree door opening for boiler controllers, 110.26(F)(1)shall provide dedicated space over controllers, with part (b) - nthere shall be no foreign piping over dedicated space, 400.8 shall not use so cord for fixed wiring, 408.4 shall provide circuit directories, 110.16 shall provide flash protection warning signs,200.6(A) shall identify grounded conductor, 110.22 shall identify disconnects
Final4/28/20094/28/20094/28/2009PPART
DetailsBob Reichert
tom Phone #: ###-#### ok to final floor 2&3 only
Electrical Rough-In4/8/20094/8/20094/8/2009PPART
DetailsMike Kinnear
jason Phone #: ###-#### ok ri 3rd floor anop
Electrical Rough-In3/23/20093/24/20093/24/2009APART
DetailsJack Frank
Jason Phone #: front entry walls and hard ceing anop
Electrical Rough-In3/9/20093/10/20093/10/2009APASS
DetailsMike Kinnear
Jason Phone #: ###-#### ok cover grid ceiling asop
Permanent Service2/11/20092/12/20092/12/2009APASS
DetailsBob Reichert
jason Phone #: ###-#### corrections made, p/s u/g n ok, 4 meters
Electrical Rough-In2/3/20092/3/20092/3/2009PPASS
DetailsBob Reichert
jason Phone #: ###-#### south stair walls only ok to cover anop
Permanent Service2/3/20092/3/20092/3/2009PFAIL
DetailsBob Reichert
jason Phone #: ###-#### met contractor, NEC 110.3 lugs for service disconnects shall be per listing and labelling for neutral and ground and installed per instructions
Electrical Rough-In1/23/20091/26/20091/26/2009APART
DetailsJack Frank
jason Note: ceiling Phone #: 353-174
outside soffit west entry
Electrical Rough-In1/20/20091/20/20091/20/2009PPASS
DetailsBob Reichert
JASON Phone #: ###-#### walls for patio and stairwells ok to cover anop
Permanent Service1/20/20091/20/20091/20/2009PCANC
DetailsBob Reichert
JASON Phone #: ###-#### see conference
Conference1/20/20091/20/20091/20/2009PDONE
DetailsBob Reichert
JASON Phone #: ###-#### reviewed grounding for services and labelling, terminations
Electrical Rough-In12/17/200812/18/200812/18/2008PPART
DetailsJack Frank
dale Phone #: ###-#### parapet wiring roof ok anop
Conference12/16/200812/17/200812/17/2008ADONE
DetailsBob Reichert
dale Phone #: ###-#### talked about re-route of fire pump conduit from service. They will re-route broken u/g
Electrical Rough-In9/29/20089/30/20089/30/2008APASS
DetailsBob Reichert
Dale- Underground Phone #: ###-#### ok to cover u/g for communications east side building, electrical contractor installed
Electrical Rough-In9/25/20089/25/20089/25/2008PPASS
DetailsBob Reichert
dale - uffer Phone #: ###-#### concrete encased electrode ok to pour
Electrical Rough-In9/5/20089/8/20089/8/2008APART
DetailsBob Reichert
dale- underground Phone #: ###-#### ok to cover u/g from temp pole south toward street- will put splice box in planter, will cut street later for generator feeders
Electrical Rough-In8/25/20088/26/20088/26/2008APASS
DetailsBob Reichert
Dale- first thing if possible Phone #: ###-#### east side u/g ok to cover under building
Electrical Rough-In8/20/20088/21/20088/21/2008APART
DetailsPat Lass
Dale Phone #: ###-####
from electrical room 30 ft east ok to cover underground
Electrical Rough-In8/19/20088/20/20088/20/2008PCANC
DetailsBob Reichert
Dale Phone #: ###-#### see conference
Conference8/20/20088/20/20088/20/2008PDONE
DetailsBob Reichert
Dale Phone #: ###-#### talked with electrical contractor about being ready for inspection, doing in parts for u/g because of depth and sluff box, conduit spacers side by side and top cover row, meters at transformer, but contractor doing work up to disconnects inside building, so city will inspect, general calling in inspections, so electrical contractor will have to co-ordinate when inspection to be requested
Electrical Rough-In8/6/20088/7/20088/7/2008APASS
DetailsBob Reichert
Dale Phone #: ###-#### ok to cover u/g for site lighting only- south box then west side of lot to north box