Final | 12/10/2008 | 12/10/2008 | 12/10/2008 | P | PASS |
Bob Reichert
|
|
|
garage code 4548 Phone #: ###-#### Internet Inspection Request from: Therrin Robertson ok to final
|
Rough-In Permanent Service | 8/26/2008 | 8/26/2008 | 8/26/2008 | A | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson see ri, p/s done
|
Electrical Rough-In | 8/26/2008 | 8/26/2008 | 8/26/2008 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson corrections made, ric ok, p/s done before
|
Rough-In Permanent Service | 8/19/2008 | 8/19/2008 | 8/19/2008 | P | CANC |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson see ri and p/s
|
Electrical Rough-In | 8/19/2008 | 8/19/2008 | 8/19/2008 | P | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called, left message, left correction notice, NEC 210.52(A) shall provide receptacles in wall space over 2' - entry, back of room, 334.30 nm cable shall not be stapled on edge, 300.4(A) edge of bored holes shall be 1 1/4" from face of framing members or protected by steel plates, BCC shall provide boxes for cables, shall have approved plans on job
|
Permanent Service | 8/19/2008 | 8/19/2008 | 8/19/2008 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson p/s u/g n ok, check for intersystem bonding bar at final
|