Permanent Service | 10/21/2008 | 10/22/2008 | 10/22/2008 | A | CANC |
Bob Reichert
|
|
|
PAUL Phone #: ###-#### Internet Inspection Request from: Sean DeLacy wrong type inspection request, see final no esc this project
|
Final | 10/22/2008 | 10/22/2008 | 10/22/2008 | A | PASS |
Bob Reichert
|
|
|
PAUL Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok to final core and shell, signed structural card, panels ok for seals, checked baths, no esc this project
|
Rough-In Permanent Service | 10/15/2008 | 10/16/2008 | 10/16/2008 | P | PART |
Pat Lass
|
|
|
PAUL Phone #: ###-#### Internet Inspection Request from: Sean DeLacy switch gear ok
|
Conference | 9/26/2008 | 9/29/2008 | 9/29/2008 | A | CANC |
Jim Schmer
|
|
|
PAUL Phone #: ###-#### Internet Inspection Request from: Sean DeLacy panel bussing can be replaced in old panel with new doors and etc. There will be no air gaps around panel at all or they will not be approved. Sealing SHALL not be with combustible material. JMS
|
Conference | 9/23/2008 | 9/24/2008 | 9/24/2008 | A | DONE |
Bob Reichert
|
|
|
DAVE Phone #: ###-#### Internet Inspection Request from: Sean DeLacy met contractor, ok to saw-cut floor and provide depressed floor and to move false ceiling to allow gear to fit without going in between floor joists, they will either put in small sump pump or curbing in floor, no esc this project
|
Conference | 9/22/2008 | 9/23/2008 | 9/23/2008 | A | PART |
Pat Lass
|
|
|
PAUL Phone #: ###-#### Internet Inspection Request from: Sean DeLacy talked with paul about the switch gear and saw it put together I told him that we have to try to get gear that will fit and if that is impossible we might justify a reduction in clearance that provides comparable safety. also in order to replace only guts to exixting panels they would have to be an exact fit.
|
Conference | 9/15/2008 | 9/16/2008 | 9/16/2008 | A | PART |
Pat Lass
|
|
|
SCOTT Phone #: ###-#### Internet Inspection Request from: Sean DeLacy talked about clearance for new switch gear
|
Electrical Rough-In | 9/2/2008 | 9/2/2008 | 9/2/2008 | P | PART |
Pat Lass
|
|
|
SCOTT BATHROOM Phone #: ###-#### Internet Inspection Request from: Sean DeLacy grape escape bathroom ok
|
Final | 8/27/2008 | 8/27/2008 | 8/27/2008 | P | PART |
William E Thomas
|
|
|
SCOTT BATHROOMS Phone #: ###-#### Internet Inspection Request from: Sean DeLacy . .1. see other for this date. . .
|
Electrical Rough-In | 8/20/2008 | 8/20/2008 | 8/20/2008 | P | PASS |
Mike Kinnear
|
|
|
Phone #: ###-#### Internet Inspection Request from: Tyler Bowen ok cover 2 bathrms anop note t/w scott they needed to get the address corrected or no more inspection. no esc permit in project
|
Conference | 8/12/2008 | 8/12/2008 | 8/12/2008 | A | PART |
Pat Lass
|
|
|
SCOTT Phone #: ###-#### Internet Inspection Request from: Sean DeLacy talked about GFCIs and permits
|