Permanent Service | 8/27/2008 | 8/28/2008 | 8/28/2008 | A | CANC |
Jack Frank
|
|
|
ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten p/s u/g rec. ok
|
Final | 8/28/2008 | 8/28/2008 | 8/28/2008 | A | PASS |
Jack Frank
|
|
|
ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten called contr will will install GEC conductor under approved lug
|
Rough-In Permanent Service | 8/26/2008 | 8/26/2008 | 8/26/2008 | P | FAIL |
Jack Frank
|
|
|
service is ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten corr called 250.64(E) shall choke both ends of nipple for GEC, 200.2(B) terminte GEC at neutral bus loose bond screw
|
Rough-In Permanent Service | 8/25/2008 | 8/26/2008 | 8/26/2008 | A | CANC |
Jack Frank
|
|
|
service is ready for inspection Phone #: ###-#### Internet Inspection Request from: gary batten Inspection cancelled from web by: gary batten
|