ELE-Aging Inspection | 7/29/2009 | 7/29/2009 | 7/29/2009 | | CANC |
Jack Frank
|
|
|
|
DOC - Permit Expired | 7/29/2009 | 7/29/2009 | 7/29/2009 | P | PASS |
Jack Frank
|
|
|
|
ELE-Aging Inspection | 3/24/2009 | 3/24/2009 | 3/24/2009 | | PART |
Jack Frank
|
|
|
waiting for contr to request final
|
ELE-Aging Inspection | 1/19/2009 | 1/19/2009 | 1/20/2009 | | PART |
Jack Frank
|
|
|
wsuc
|
ELE-Aging Inspection | 11/18/2008 | 11/18/2008 | 11/18/2008 | | PART |
Jack Frank
|
|
|
talked to clyde he will call when ready
|
Permanent Service | 9/18/2008 | 9/18/2008 | 9/18/2008 | P | PASS |
Jack Frank
|
|
|
Clide- call 30 min prior to going Phone #: ###-#### p/s o/h rec.
|
Rough-In Permanent Service | 8/25/2008 | 8/26/2008 | 8/26/2008 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### corr. called 110.26(F)(2) remove gas pipe below p/s, 250.52 (A)(1) or 104(A)(1) grd or bond water pipe, 310.16 needs 250 KC mill 310.8 needs sunlight resistence wire
|