Electrical Rough-In | 9/12/2008 | 9/12/2008 | 9/12/2008 | P | PASS |
Jack Frank
|
|
|
Stu Phone #: ###-####ok
|
Final | 9/12/2008 | 9/12/2008 | 9/12/2008 | P | PASS |
Jack Frank
|
|
|
Stu Phone #: ###-#### ok card signed
|
Final | 9/11/2008 | 9/12/2008 | 9/12/2008 | A | NR |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 9/11/2008 at 9:54:04 PM. Contact: ###-####. see failed ri, fee due
|
Electrical Rough-In | 9/11/2008 | 9/12/2008 | 9/12/2008 | A | FAIL |
Bob Reichert
|
|
|
Stu- ceiling Phone #: ###-#### met electrician, left correction notice, NEC 725.25 abandoned class 2,3,PLTC cables shall be removed, 300.11(A) shall securely support raceways and cable assemblies, 348.30(A) shall securely support fmc within 12" of termination,358.30(A) shall securely support emt within 3' of termination, BCC no violations shall be retained, no cables or raceways shall be supported by grid or tiles, no esc this project
|
Electrical Rough-In | 8/26/2008 | 8/26/2008 | 8/26/2008 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Stuart Welton walls only ok to cover , left correction notice BCC 4-05-33(A),(B) no violations shall be retained, no esc this project
|