Final | 10/13/2009 | 10/14/2009 | 10/14/2009 | A | PASS |
Jack Frank
|
|
|
steve Phone #: ###-#### ok
|
Final | 10/12/2009 | 10/13/2009 | 10/13/2009 | A | FAIL |
Jack Frank
|
|
|
ELECTRICIAN STEVE ###-#### - LUKE ###-#### Phone #: ###-#### Internet Inspection Request from: Dave Koeppen corr called box fill peninsular counter recept, had no power or access to j tub recepts
|
Electrical Rough-In | 10/6/2008 | 10/7/2008 | 10/7/2008 | A | PASS |
Jack Frank
|
|
|
Luke Phone #: ###-#### ok
|
Permanent Service | 10/7/2008 | 10/7/2008 | 10/7/2008 | A | PASS |
Jack Frank
|
|
|
Luke Phone #: ###-#### p/s u/g new ok
|
Electrical Rough-In | 10/1/2008 | 10/2/2008 | 10/2/2008 | A | FAIL |
Bob Reichert
|
|
|
luke Note: cover up Phone #: ###-#### called, left message, left corr notice, NEC 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of faming members, 300.14 shall have 6" free conductor length in boxes, 314.5 shall support nm cable within 8" of boxes, 314.23 boxes shall be rigidly supported, 210.52(D) bath receptacle shall be within 3' of edge of basin, 210.52(A) receptacles shall be installed in wall space over 2", 110.26(F) there shall not be a/c lines in dedicated space over panel,300.5 u/g to post lights shall be minimum 18" deep, BCC shall provide boxes in bath areas, shall change room count to 17 rooms on permit, no esc this project
|