Final | 11/20/2008 | 11/21/2008 | 11/21/2008 | A | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters corrections made, ok to final
|
Final | 11/13/2008 | 11/14/2008 | 11/14/2008 | A | FAIL |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters called, left correction norice, NEC 511.12 receptacles in shop area shall be gfci protected for 125v, 15 and 20a, 110.26(F)(1) there shall not be any foreign piping or systems in dedicated panel space-panel c, 400.8 flexible cord shall not be used as a substitute for fixed wiring(Hotsy), (parts cleaner), BCC 4-05-33(A)(B) all equipment shall be listed by a nationally recognized testing laboratory (Hotsy), (parts cleaner)
|
Electrical Rough-In | 11/7/2008 | 11/7/2008 | 11/7/2008 | P | PASS |
Bob Reichert
|
|
|
Ceiling Phone #: ###-#### Internet Inspection Request from: Celinda Winters ok to cover ceilings bathrooms and offices only
|
Electrical Rough-In | 10/30/2008 | 10/31/2008 | 10/31/2008 | A | PART |
Jack Frank
|
|
|
wall rough-in in restroom Phone #: ###-#### Internet Inspection Request from: Celinda Winters ok
|
Electrical Rough-In | 10/20/2008 | 10/20/2008 | 10/20/2008 | A | PASS |
Bob Reichert
|
|
|
Wall rough-in in new offices Phone #: ###-#### Internet Inspection Request from: Celinda Winters ok to cover office area walls only
|
Permanent Service | 9/19/2008 | 9/19/2008 | 9/19/2008 | P | PASS |
Bob Reichert
|
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters p/s u/g n ok
|