Permit Information
Permit NumberELE08-02410
StatusFinaled
Name WINTERS ELECTRIC LLC
Site Address 2405 S JANEEN ST
Project Name 
Customer Number08237
ePlanReview 
Description
Electrical Permit - Addition: new service - office addition
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final11/20/200811/21/200811/21/2008APASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Celinda Winters corrections made, ok to final
Final11/13/200811/14/200811/14/2008AFAIL
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Celinda Winters called, left correction norice, NEC 511.12 receptacles in shop area shall be gfci protected for 125v, 15 and 20a, 110.26(F)(1) there shall not be any foreign piping or systems in dedicated panel space-panel c, 400.8 flexible cord shall not be used as a substitute for fixed wiring(Hotsy), (parts cleaner), BCC 4-05-33(A)(B) all equipment shall be listed by a nationally recognized testing laboratory (Hotsy), (parts cleaner)
Electrical Rough-In11/7/200811/7/200811/7/2008PPASS
DetailsBob Reichert
Ceiling Phone #: ###-#### Internet Inspection Request from: Celinda Winters ok to cover ceilings bathrooms and offices only
Electrical Rough-In10/30/200810/31/200810/31/2008APART
DetailsJack Frank
wall rough-in in restroom Phone #: ###-#### Internet Inspection Request from: Celinda Winters ok
Electrical Rough-In10/20/200810/20/200810/20/2008APASS
DetailsBob Reichert
Wall rough-in in new offices Phone #: ###-#### Internet Inspection Request from: Celinda Winters ok to cover office area walls only
Permanent Service9/19/20089/19/20089/19/2008PPASS
DetailsBob Reichert
Phone #: ###-#### Internet Inspection Request from: Celinda Winters p/s u/g n ok