Final | 10/29/2008 | 10/30/2008 | 10/30/2008 | P | PASS |
Jack Frank
|
|
|
Scheduled by a contractor via Hello! on 10/29/2008 at 3:45:39 PM. Contact: ###-####. ok
|
Electrical Rough-In | 9/5/2008 | 9/5/2008 | 9/5/2008 | P | PASS |
Bob Reichert
|
|
|
Scheduled by a contractor via Hello! on 9/5/2008 at 9:41:18 AM. Contact: ###-####. corrections made, ric ok
|
Electrical Rough-In | 9/4/2008 | 9/5/2008 | 9/5/2008 | A | FAIL |
Bob Reichert
|
|
|
john Phone #: ###-#### called, left correction notice, NEC 300.14 at least 6" free conductor shall be left at each outlet point, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, 334.30 flat nm cable shall not be stapled on edge
|