Final | 11/17/2008 | 11/18/2008 | 11/18/2008 | A | PASS |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Sean Peltier ok
|
Rough-In Permanent Service | 9/9/2008 | 9/10/2008 | 9/10/2008 | A | PASS |
Jack Frank
|
|
|
please reinspect, can we survey the nmb on the porch? the owner is puting soffit material in a few weeks Phone #: ###-#### Internet Inspection Request from: Sean Peltier still needs recept and disconnect for a/c, r/i soffit ok p/s o/h rec. ok
|
Rough-In Permanent Service | 9/9/2008 | 9/9/2008 | 9/9/2008 | A | FAIL |
Jack Frank
|
|
|
Phone #: ###-#### Internet Inspection Request from: Sean Peltier corr. called 334.12(B)(4) shall not use NM cable in damp locations, 250.104(A)(1) bond water piping back to service, 200.7 ID neutral used as phase in cable, 250.8 no SMS for grds or bonds, jbox (old panel), 230.24(A) needs 8ft clearence for drop, T310.16 #12 on 30 amp breaker (a/c) also no violation retained for a/c wiring needs gfci recept and disconnect, 408.4 be specific panel schedules house and shop
|