Final | 1/5/2009 | 1/5/2009 | 1/5/2009 | P | PASS |
Jack Frank
|
|
|
Electrical Final Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe ok
|
Electrical Rough-In | 9/30/2008 | 10/1/2008 | 10/1/2008 | P | PASS |
Jim Schmer
|
|
|
REINSPECTION FOR ELECTRICAL ROUGH-IN...PLEASE CALL JAKE ( ROWDY IS OUT OF STATE UNTIL 10/6/08 ) Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe
|
Electrical Rough-In | 9/29/2008 | 9/30/2008 | 9/30/2008 | A | FAIL |
Jack Frank
|
|
|
Electrical Rough-in Internet Inspection Request from: Rowdy Monroe corr called left message 210.52 (A,B,C) needs outlet for 2ft wall kit, din rm shall be on SABC ,shall not feed liv rm from it, needs outlets for countertop in breakfast nook, BCC shall complete all wiring install all b oxes upstairs ceilings
|
Rough-In Permanent Service | 9/15/2008 | 9/16/2008 | 9/16/2008 | A | PART |
Pat Lass
|
|
|
Rough-in Service Inspection Internet Inspection Request from: Rowdy Monroe no R/I yet P/S O/H R Ok to transfer power
|